Traduciendo...
7302
Encoder Phase A/B Swapped
ABB · ACS800 Standard Firmware
¿Qué significa 7302 ?
The pulse encoder phasing is incorrect, specifically Phase A is connected to the terminal for Phase B and vice versa. This will result in incorrect speed or position feedback, potentially causing motor rotation direction issues or control instability.
Causas comunes
- Incorrect wiring of encoder phase signals A and B.
- Encoder signals A and B are reversed in the control unit configuration (P3-01, P3-02).
- Faulty encoder sensor generating swapped phase signals.
- Improper installation or setup of the encoder feedback.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Interchange the physical connections of pulse encoder phases A and B at the drive's encoder terminal block.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: ABB ACS800 Standard Firmware