9000
EXTERNAL FLT
ABB · ACS800 Standard Firmware
¿Qué significa 9000 ?
A fault has been triggered by an external device connected to the drive. This fault is typically configured to activate via one of the drive's programmable digital inputs. It is associated with bit 8 of Fault Word 2 (3.06 FW 2) and programmable via Fault Function 30.03.
Causas comunes
- External control signal indicating a fault condition.
- Input terminal (e.g., DI1-DI5) configured for external fault is active.
- Interlock or safety circuit triggered by an external device.
- Alarm signal received from a connected peripheral equipment.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Identify the specific external device(s) connected to the drive's digital inputs that are configured to trigger this fault.
- 2
Inspect the identified external device(s) for any active fault conditions, operational issues, or power loss.
- 3
Verify the configuration of parameter 30.03 (EXTERNAL FAULT) and the associated digital input terminal to ensure correct fault triggering logic.
Datos técnicos verificados. Última actualización: March 2026