PDO data is not present (Cn to Mn) (_ecPDO_DATA_MISSING_CN_TO_MN)

ABB · ACS850 Standard Program Firmware

¿Qué significa 10030 ?

This fault indicates a loss of Process Data Object (PDO) communication between a remote axis (Client Node, CN) and the manager (Master Node, MN), specifically when at least two consecutive PDO packets are not received. For a NextMove e100, it means a drive has disappeared from the network. Unresolved, this can lead to loss of control over the remote axis and system instability.

Causas comunes

  • Intermittent or broken EtherCAT communication cable (e.g., CAT5e/CAT6) between the Master Node and Client Node.
  • Incorrect EtherCAT network configuration (e.g., Master Node not mapping expected PDOs from Client Node).
  • Client Node (drive) power cycling or temporary power loss causing it to drop off the network.
  • Excessive electromagnetic interference (EMI) on the EtherCAT network cable disrupting data packets.
  • Master Node's cycle time too short or Client Node's response time too slow, leading to missed PDOs.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Inspect the EtherCAT cable between the Master Node and Client Node for physical damage, ensuring secure connections at both RJ45 ports.

  2. 2

    2. Verify the EtherCAT cable shield is properly terminated at the master and slave devices to mitigate EMI.

  3. 3

    3. Check the Master Node's configuration file for correct PDO mapping and update rates for the Client Node.

  4. 4

    4. Monitor the network status LEDs on both the Master and Client Node (e.g., EtherCAT Link/Activity LEDs) for link integrity.

  5. 5

    5. Review the Master Node's diagnostic log for specific communication errors related to the Client Node ID.

  6. 6

    6. Temporarily reduce the EtherCAT Master's cycle time or increase the watchdog timeout period (if configurable) to test for timing issues.