FF38

HW RECONF RQ

ABB · ACS800

¿Qué significa FF38 ?

The inverter type (e.g., sr0025_3) of the ABB ACS800 drive has been changed, typically during factory setup or drive implementation. This alarm indicates that the new inverter hardware configuration needs to be validated by a power cycle of the control board.

Causas comunes

  • A change in the inverter type or configuration has been detected by the drive's system.
  • New hardware components requiring re-initialization have been installed or configured.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Acknowledge the 'HW RECONF RQ' alarm and wait for the subsequent 'POWEROFF!' (FF39) alarm to activate.

  2. 2

    Switch the control board power of the ABB ACS800 drive off completely using the main disconnect.

  3. 3

    Power on the control board again to allow the drive to validate the inverter type change and reconfigure its hardware settings.

  4. 4

    Verify that the inverter type shown in the drive's monitoring parameters matches the physical unit after the power cycle.