001A
USER PROGRAM INCOMPATIBLE WITH OS AT POWER-UP
Allen-Bradley · MicroLogix 1400 Programmable Controllers
¿Qué significa 001A ?
At power-up, the user program loaded into the controller is found to be incompatible with its Operating System (OS). This is a non-user fault preventing the controller from starting correctly, similar to a memory module incompatibility but occurring during initial program load.
Causas comunes
- Controller OS version does not support features or instructions used in the user program.
- User program was developed for a different controller series or OS version.
- Corrupted program download that resulted in an incompatible state.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Upgrade the controller's OS using ControlFLASH to a compatible version that supports all instructions in the user program.
- 2
Contact your local Rockwell Automation representative for more information about available operating systems compatible with your controller and user program.