0022

WATCHDOG TIMER EXPIRED, SEE S:3

Allen-Bradley · MicroLogix 1400 Programmable Controllers

¿Qué significa 0022 ?

The program scan time exceeded the configured watchdog timeout value, which is stored in status file S:3H. This is a nonrecoverable fault, indicating that the controller's program took too long to execute, potentially due to an infinite loop, excessive processing, or an incorrectly set watchdog timer.

Causas comunes

  • Program logic is caught in an infinite or excessively long loop.
  • Excessive processing load due to complex calculations or communication tasks during a single scan.
  • Watchdog timeout value in status file S:3H is set too low for the program's complexity and execution time.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Review the program logic to identify and correct any infinite loops or sections that take an extended time to execute.

  2. 2

    Increase the watchdog timeout value in status file S:3H, but ensure it remains appropriate for the application's safety and response time requirements.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas