Traduciendo...
ERR_SOCKET_BIND

Socket error during Bind operation

Allen-Bradley · MicroLogix 1400 Programmable Controllers

¿Qué significa ERR_SOCKET_BIND ?

An error occurred during the socket bind operation. This prevents the Modbus TCP server from associating a local IP address and port with the socket, indicating a problem with the configured network interface or port availability.

Causas comunes

  • Specified IP address for Modbus TCP server is invalid or not assigned to an active network interface.
  • Modbus TCP port (default 502) is already in use by another application.
  • Network interface is down or incorrectly configured.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the Modbus TCP server's configured IP address is correct and active on the controller's network interface.

  2. 2

    Check if the Modbus TCP port (default 502) is already in use by another service on the controller.

  3. 3

    Restart the controller to clear potential port conflicts and network interface issues.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Allen-Bradley MicroLogix 1400 Programmable Controllers