Device overtemperature shutdown
Bosch Rexroth · IndraDrive C Drive Controllers
¿Qué significa F2018 ?
The drive controller or associated power electronics have reached a critical internal temperature, triggering a safety shutdown to prevent damage. This is a severe thermal event.
Causas comunes
- Inadequate cooling for the drive due to blocked vents, fan failure, or high ambient temperature.
- Sustained operation at or above the drive's rated output current.
- Internal thermal sensor malfunction or incorrect reading.
- Failure of internal cooling components.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Allow the drive controller to cool down completely before attempting to reset the fault.
- 2
Check the drive's cooling fan for proper operation. Verify airflow direction and ensure no obstructions in the heatsink or ventilation openings.
- 3
Measure the ambient temperature around the drive and ensure it is within the specified operating range.
- 4
Reduce the load on the drive if possible, or verify that the drive is correctly sized for the application's continuous and peak current requirements.