Traduciendo...
F2028

Excessive deviation

Bosch Rexroth · IndraDrive C Drive Controllers

¿Qué significa F2028 ?

The actual position or velocity deviates excessively from the commanded value. This indicates a loss of control or an inability of the drive to follow the motion profile.

Causas comunes

  • Mechanical binding, obstruction, or excessive load preventing the motor from following commands.
  • Incorrect control loop tuning (e.g., P, I, D gains) resulting in instability or sluggish response.
  • Faulty motor or encoder feedback, leading to inaccurate actual value reporting.
  • Drive undersized for the application's inertia or acceleration requirements.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the mechanical system for any binding, blockage, or excessive friction that would prevent the motor from moving freely.

  2. 2

    Verify the motor and encoder cabling for secure connections, proper shielding, and continuity.

  3. 3

    Check the drive's control loop parameters (e.g., position loop gain, velocity loop gain) and re-tune if necessary, starting with lower gains.

  4. 4

    Ensure the motor and drive are correctly sized for the application's inertia and dynamic requirements.

Ver todos los códigos en este manual (66)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Bosch Rexroth IndraDrive C Drive Controllers