F8201

Fatal Error (Safety Technology Initialization)

Bosch Rexroth · IndraDrive C Drive Controllers

¿Qué significa F8201 ?

This is a fatal error specifically tied to the drive's safety technology during initialization. When F8201 occurs, the closed-loop or open-loop U/f control of the drive is no longer guaranteed. The drive immediately switches off, becoming torque-free, overriding settings in P-0-0119 and P-0-0117. This error requires a complete recommissioning of the safety technology.

Causas comunes

  • An error condition detected within the drive's safety technology system during initialization.
  • Safety technology requires complete recommissioning.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Switch the drive off completely.

  2. 2

    Recommission the safety technology completely.

  3. 3

    Clear the error message using command S-0-0099 (C0500 Reset class 1 diagnostics). This may require switching to parameter mode or a complete drive power cycle.

  4. 4

    Ensure the drive is in operating mode and power is switched on ("Ab").

  5. 5

    Switch on drive enable again (0-1 edge).

  6. 6

    If this fatal error recurs repeatedly, replacement of an entire component (e.g. motor or drive controller) may be necessary.