Traduciendo...
F8203

Fatal Error (Safety Technology Initialization)

Bosch Rexroth · IndraDrive C Drive Controllers

¿Qué significa F8203 ?

This is a fatal error specifically tied to the drive's safety technology during initialization. When F8203 occurs, the closed-loop or open-loop U/f control of the drive is no longer guaranteed. The drive immediately switches off, becoming torque-free, overriding settings in P-0-0119 and P-0-0117. This error requires a complete recommissioning of the safety technology.

Causas comunes

  • An error condition detected within the drive's safety technology system during initialization.
  • Safety technology requires complete recommissioning.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Switch the drive off completely.

  2. 2

    Recommission the safety technology completely.

  3. 3

    Clear the error message using command S-0-0099 (C0500 Reset class 1 diagnostics). This may require switching to parameter mode or a complete drive power cycle.

  4. 4

    Ensure the drive is in operating mode and power is switched on ("Ab").

  5. 5

    Switch on drive enable again (0-1 edge).

  6. 6

    If this fatal error recurs repeatedly, replacement of an entire component (e.g. motor or drive controller) may be necessary.

Ver todos los códigos en este manual (66)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Bosch Rexroth IndraDrive C Drive Controllers