Live zero error

Danfoss · VLT HVAC Drive FC 102

¿Qué significa 2 ?

This warning or alarm appears if programmed in 6-01 Live Zero Timeout Function. It indicates that the signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. Common causes include broken wiring or a faulty device sending the signal, which can lead to incorrect process control.

Causas comunes

  • Analog input signal (e.g., from terminal 53A or 53B) falling below 50% of the programmed minimum value (P6-02).
  • Open circuit or high resistance in the wiring connecting the analog sensor to the drive's input terminals.
  • Sensor failure resulting in an output signal consistently below its specified minimum range.
  • Incorrect configuration of parameter P6-01 (Live Zero Timeout Function) for the specific analog input signal type.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the voltage or current signal at the analog input terminal (e.g., 53A/53B or 60/61) and verify it's above 50% of the minimum value set in P6-02.

  2. 2

    Verify parameters P6-02 (Minimum Reference) and P6-03 (Maximum Reference) are correctly configured for the connected analog sensor's range.

  3. 3

    Check continuity of the sensor signal cable from the sensor output to the drive's analog input terminals using a multimeter.

  4. 4

    Calibrate or replace the analog sensor if its output signal is consistently below the expected minimum at a known process value.