Traduciendo...
51

AMA check U nom and I nom

Danfoss · VLT HVAC Drive FC 102

¿Qué significa 51 ?

The settings for motor voltage, motor current, or motor power are incorrect, preventing successful Automatic Motor Adaptation (AMA). Incorrect motor data can lead to poor motor control, reduced efficiency, and inadequate motor protection. This also impacts the drive's ability to properly characterize the motor.

Causas comunes

  • Incorrect nominal motor voltage (P1-21) or nominal motor current (P1-22) entered compared to the motor nameplate.
  • Motor power (P1-20) setting is incompatible with the frequency converter's rated output current capability.
  • Discrepancy between the motor's actual electrical characteristics and the values configured in the drive.
  • Drive is significantly undersized for the connected motor, or the motor is outside the drive's recommended operating range.
  • Motor winding resistance or inductance values falling outside the expected range for the entered nominal data.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Compare the motor nameplate data for nominal voltage, current, and power directly against parameters P1-21, P1-22, and P1-20 in the drive.

  2. 2

    Correct any discrepancies found in P1-21 (Motor Voltage), P1-22 (Motor Current), or P1-20 (Motor Power) based on the motor nameplate.

  3. 3

    Ensure the drive's nominal output current (specified on the drive nameplate) is greater than or equal to the motor's nominal current (P1-22).

  4. 4

    Verify P1-23 (Motor Frequency) and P1-24 (Motor Speed) are also correctly entered according to the motor nameplate.

  5. 5

    Perform a static AMA (if available via P1-25 AMA Type) to see if it provides more robust motor identification.