Traduciendo...
ALARM 2

Live zero error

Danfoss · VLT HVAC Drive High Power

¿Qué significa ALARM 2 ?

The signal on one of the analog inputs is less than 50% of the programmed minimum value. This condition, appearing if parameter 6-01 Live Zero Timeout Function is programmed, often indicates broken wiring or a faulty sensor/device sending the analog signal, risking incorrect operation or control.

Causas comunes

  • Broken wire or loose connection in the analog input signal path (e.g., between sensor and AI terminal 53).
  • Sensor failure, providing an output signal below its specified live zero threshold (e.g., 4-20mA signal dropping below 2mA).
  • Incorrect scaling of the analog input in parameter 6-10 (Low Reference) or 6-11 (High Reference), leading to misinterpretation of a low signal.
  • External electrical noise interfering with the low-level analog signal, causing spurious readings.
  • Faulty analog input module on the frequency converter's control board.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the analog input signal at the sensor output terminals using a multimeter (e.g., set to mA or VDC).

  2. 2

    Measure the analog input signal directly at the frequency converter's input terminals (e.g., terminal 53 to 55) to confirm signal presence.

  3. 3

    Inspect wiring for continuity and secure connections from the sensor to the frequency converter's analog input terminals.

  4. 4

    Check parameter 6-01 (Live Zero Timeout Function) to ensure it is correctly configured for the sensor type and application.

  5. 5

    Review parameter 6-10 (Low Reference) and 6-11 (High Reference) settings to accurately match the sensor's output range.

  6. 6

    Replace the analog input sensor if its output consistently remains below the expected live zero despite proper wiring.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT HVAC Drive High Power