ALARM 7

DC overvoltage

Danfoss · VLT HVAC Drive High Power

¿Qué significa ALARM 7 ?

The DC-link voltage has exceeded its limit, causing the frequency converter to trip after a certain time. This often occurs due to regenerative braking or excessive mains voltage, which can damage the inverter section if not mitigated.

Causas comunes

  • Excessively high incoming AC mains voltage, consistently above the frequency converter's maximum input voltage.
  • Rapid deceleration of a high inertia load, causing significant regenerative energy feedback to the DC link.
  • Braking resistor failure (open circuit) or incorrect sizing (too high resistance) if installed.
  • Deceleration ramp time (P3-42, P3-44) set too short for the application, generating excessive regenerative voltage.
  • Fault in the frequency converter's DC-link measurement or protection circuitry.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) and confirm it is within the frequency converter's specified operating range.

  2. 2

    Increase the deceleration ramp time (P3-42 for ramp 1, P3-44 for ramp 2) to allow for slower energy dissipation.

  3. 3

    Verify the connection and resistance of the external braking resistor (if present) and ensure it matches the value specified in P2-11 (Brake Resistor Ohms).

  4. 4

    Consider implementing a brake chopper and resistor combination or a regenerative front end for high inertia applications.

  5. 5

    Review the application for external forces causing motor regeneration, such as overhauling loads or rapid changes in load direction.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026