Traduciendo...
WARNING 6

DC link voltage low

Danfoss · VLT HVAC Drive High Power

¿Qué significa WARNING 6 ?

The DC-link voltage is lower than the warning limit, which depends on the frequency converter's voltage rating. The unit remains active but operating at a reduced DC link voltage can affect motor performance or lead to an undervoltage trip.

Causas comunes

  • Low incoming AC mains voltage or significant voltage sag below 340V during heavy load transients.
  • Loose or high-resistance connections on the incoming AC mains terminals (L1, L2, L3).
  • Insufficiently sized or overly long mains supply cables, leading to excessive voltage drop under load.
  • Overloading the frequency converter beyond its rated capacity, causing high current draw and voltage sag.
  • Faulty input rectifier bridge or DC-link capacitor bank within the frequency converter.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) under load and verify it is within the frequency converter's specified operating range.

  2. 2

    Check for loose or corroded connections on the frequency converter's input terminals (L1, L2, L3).

  3. 3

    Review the cable sizing for the mains supply to ensure it is adequate for the frequency converter's current rating and cable length.

  4. 4

    Monitor the DC-link voltage on the frequency converter's display (parameter 16-01 DC Link Voltage) during operation to identify sag events.

  5. 5

    Reduce the motor load or consider a higher-rated frequency converter if continuous low DC-link voltage is observed under normal operating conditions.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT HVAC Drive High Power