CC%2 operating mode not possible
Heidenhain · TNC CNC Controllers
¿Qué significa 231-A040 ?
This error indicates that the current combination of operating mode switches and protective door statuses is not permissible for the CC%2 controller. This can result from incorrect switch settings, open safety doors, or faulty wiring.
Causas comunes
- The status of the operating mode switches and protective doors is not allowed.
- Incorrect setting of one or more operating mode switches.
- Safety doors are not in the required state (e.g., open when they should be closed).
- Wiring error in the operating mode selection or safety door circuits.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the current setting of all operating mode switches and ensure they correspond to a permissible configuration.
- 2
Verify the status of all safety doors; ensure they are closed and locked if required for the selected operating mode.
- 3
Inspect the wiring associated with the operating mode switches and safety door sensors for continuity, damage, or loose connections.
- 4
Consult the machine documentation to understand the valid combinations of operating modes and safety door statuses.