Traduciendo...
2034

Grid overvoltage

Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter

¿Qué significa 2034 ?

The grid voltage exceeds the upper threshold or the high voltage duration has lasted for more than the value specified by high voltage ride-through (HVRT). This indicates an unstable or excessively high grid voltage.

Causas comunes

  • The grid voltage exceeds the upper threshold.
  • The high voltage duration has lasted for more than the value specified by high voltage ride-through (HVRT).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Monitor if the alarm occurs occasionally, indicating a temporary power grid abnormality. The SUN2000 automatically recovers when the grid stabilizes.

  2. 2

    If the alarm persists, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. If it is, modify the grid overvoltage protection threshold through the mobile app, SmartLogger, or NMS with consent from the local power operator.

  3. 3

    Check whether the peak voltage of the power grid is too high. If the alarm persists and cannot be rectified for a long time, contact the power operator.

Ver todos los códigos en este manual (24)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Huawei SUN2000-(3KTL-10KTL)-M1 Solar Inverter