Abnormal residual current
Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter
¿Qué significa 2051 ?
The input-to-ground insulation impedance has decreased during the SUN2000 operation. This typically indicates an insulation fault or a temporary issue with external power cabling.
Causas comunes
- The input-to-ground insulation impedance has decreased during the SUN2000 operation.
- The external power cable may be abnormal temporarily.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Monitor if the alarm occurs accidentally and the SUN2000 automatically recovers after the external power cable abnormality is rectified.
- 2
If the alarm persists or lasts a long time, check whether the impedance between the PV string and ground is too low.