2031
Power grid phase wire short-circuit to PE
Huawei · SUN2000 Solar Inverter
¿Qué significa 2031 ?
The impedance of the inverter's output phase wire is low, or it is short-circuited to the Protective Earth (PE) conductor. This fault indicates a ground fault in the AC output wiring, posing safety risks and preventing grid-tied operation.
Causas comunes
- The impedance of the output phase wire is low.
- The output phase wire is short-circuited to PE.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the impedance of the output phase wire to PE.
- 2
Locate the position with lower impedance and restore that.
Datos técnicos verificados. Última actualización: March 2026