Mains phase loss fault
Indramat · CLM01.3-M Flying Cutoff Control
¿Qué significa F382 ?
With HVE power supply units only! At least one phase of the 3-phase power supply input to the HVE unit is missing, indicating a loss of input power similar to F381 but specific to HVE units.
Causas comunes
- At least one phase of the 3-phase power supply input to the HVE unit is missing.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the incoming 3-phase power supply at the input terminals of the Indramat HVE power supply unit using a multimeter. Confirm all three phases are present and balanced.
- 2
Inspect all upstream mains fuses and circuit breakers for the power supply unit. Replace any blown fuses or reset tripped breakers.
- 3
Check power contactors and their auxiliary contacts for proper operation and engagement in the power distribution circuit.
- 4
Inspect all power wiring connections from the mains supply to the HVE unit for looseness, damage, or disconnections.