Connection error at power supply unit
Indramat · CLM01.3-M Flying Cutoff Control
¿Qué significa F384 ?
With HVR power supply units only! This fault indicates that the power and control voltage connections are not in phase, specifically that terminals X5/U and X8/1, X5/V and X8/2, X5/W and X8/3 are conducting voltage to each other.
Causas comunes
- Power and control voltage connections are incorrectly wired or in phase with each other.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
De-energize the Indramat HVR power supply unit and ensure all power is locked out according to safety procedures.
- 2
Verify the wiring between the power input terminals (X5/U, X5/V, X5/W) and the control voltage input terminals (X8/1, X8/2, X8/3) for incorrect connections or cross-wiring.
- 3
Using a multimeter in continuity or resistance mode, check for unintended electrical connections or short circuits between X5/U and X8/1, X5/V and X8/2, and X5/W and X8/3. There should be no continuity.
- 4
Correct any incorrect wiring or short circuits identified between these terminal groups.