F6043

Positive travel range limit switch activated

Indramat · Indradrive

¿Qué significa F6043 ?

The hardware limit switch for the positive travel range has been activated, indicating that the axis has reached or exceeded its positive mechanical limit. This causes the drive to stop further movement in the positive direction to prevent damage.

Causas comunes

  • Mechanical overrun of the axis beyond the positive limit switch.
  • Limit switch stuck in the activated position.
  • Incorrect wiring of the limit switch or faulty input.
  • Control program error commanding movement into the positive limit.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that the axis has not mechanically overtraveled into the positive limit switch. If so, manually move it off the switch.

  2. 2

    Check the positive limit switch for physical damage or if it is stuck in the activated position.

  3. 3

    Inspect the wiring of the positive limit switch to the IndraDrive input for loose connections or damage.

  4. 4

    Review the drive's input status for the positive limit switch to confirm its signal is accurate.

  5. 5

    Adjust the motion profile or software travel limits to prevent activation of the hardware limit switch during normal operation.