Traduciendo...
26050
Fault in brake resistor, KPP/KSP (axis)
Kuka · KR C4 Controller
¿Qué significa 26050 ?
This fault indicates that the KPP drive has detected an error within the ballast (brake) circuit. This can compromise the drive's ability to dissipate regenerative energy, potentially leading to overvoltage conditions or drive damage.
Causas comunes
- Malfunction or damage to the ballast resistor
- Incorrect or damaged cabling between the KPP and the ballast resistor
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect the ballast resistor for physical damage or open circuit.
- 2
Check the cabling between the KPP and the ballast resistor for continuity and proper connection.
- 3
Reinitialize the drive bus by cycling Power Off / Power On.
- 4
Check the KPP module for any status indicators.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Kuka KR C4 Controller