Traduciendo...
PWR/3.3V Off (CIB_SR)
CIB_SR 3.3V Power Supply Not Present
Kuka · Sunrise Cabinet Med Controller
¿Qué significa PWR/3.3V Off (CIB_SR) ?
The PWR/3.3V Green LED for the CIB_SR module is OFF, indicating a lack of 3.3V supply voltage to the module. This absence of critical operating voltage prevents the CIB_SR module from functioning correctly and could result in the non-operation of interconnected I/O nodes.
Causas comunes
- The 3.3V power supply to the CIB_SR module is not present.
- Absence of 3.3V power on the CIB_SR communication interface board.
- The CIB_SR module is not receiving its required 3.3V supply voltage.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check fuse F17.3 on the CCU_SR for continuity and proper rating.
- 2
Verify the presence and correct seating of jumper plug X308.
- 3
Check fuse F308 on the CCU_SR for continuity and proper rating.
- 4
If an external supply is used via X308, check the external power supply to ensure it provides the rated voltage of 24 V.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Kuka Sunrise Cabinet Med Controller