Safety Node A Internal Fault
Kuka · Sunrise Cabinet Med Controller
¿Qué significa STAS1 Flashing ?
The STAS1 (Safety node A) Orange LED is flashing at a rate other than 1 Hz (normal) or 10 Hz (boot phase), indicating an internal fault code within Safety Node A. This suggests a problem with the internal logic, communication, or processing of this safety node, potentially affecting safety chain integrity and preventing safe operation.
Causas comunes
- Internal fault within the Safety Node A (STA1).
- Possible hardware failure on the safety controller.
- Corrupted firmware in the safety module.
- Overload or short circuit detected on a safety input/output.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check cabling at connectors X309, X310, and X312 for proper connection, integrity, and any signs of damage.
- 2
For test purposes, disconnect the cables at X309, X310, and X312, then switch the controller off and back on again to reset the module.
- 3
If the error recurs after checking cabling and power cycling, exchange the CCU_SR module.