F113
Send Failure (General)
Mitsubishi Electric · MELSEC Q-series MELSECNET/H
¿Qué significa F113 ?
A general send failure has occurred, and retrying the transmission did not resolve the issue. This indicates a persistent underlying problem in the communication path or station configuration.
Causas comunes
- Faulty network cables or incorrect wirings
- Faulty network hardware
- Electrical noise
- Absence of terminating resistors (in bus networks)
- Duplicate station numbers or duplicate control/remote master stations
- Parameter errors or incorrect switch settings on the corresponding station
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect network cables for damage, incorrect wiring, or loose connections
- 2
Verify the presence and correct installation of terminating resistors, if applicable (bus networks)
- 3
Check for sources of electrical noise
- 4
Confirm all station numbers are unique and control/remote master station settings are not duplicated
- 5
Review network parameters and switch settings to ensure the corresponding station is properly configured
- 6
Check for faulty network hardware