Traduciendo...
E35

Outdoor Heat Exchanger Sensor (ThOR) Defective or High Pressure

Mitsubishi Electric · R410A Systems

¿Qué significa E35 ?

The outdoor unit's heat exchanger sensor (ThOR) is defective (open or short circuit) or has a poor connection to the outdoor unit PCB. This can also indicate excessively high cooling pressure, compromising system efficiency and safety.

Causas comunes

  • Outdoor heat exchanger temperature sensor (ThOR) failure.
  • Sensor connection is loose or damaged.
  • High discharge pressure condition.
  • Refrigerant overcharge or blockage in the system.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the resistance of the ThOR sensor at its leads — compare to a resistance-temperature chart if available.

  2. 2

    Inspect the ThOR sensor's connector on the outdoor unit PCB — verify it is securely seated.

  3. 3

    Measure system high-side pressure using manifold gauges during cooling operation.

  4. 4

    Verify condenser coil cleanliness and airflow if high pressure is observed.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric R410A Systems