E42
Compressor Abnormally High Current
Mitsubishi Electric · R410A Systems
¿Qué significa E42 ?
The system has detected an abnormally high current draw by the compressor. This indicates an overload condition, potentially due to mechanical issues, excessively high head pressure, or an electrical fault within the compressor motor.
Causas comunes
- Compressor drawing abnormally high current.
- Compressor internal winding fault.
- Mechanical issue within the compressor.
- Low voltage supply to the compressor.
- Overload condition on the compressor circuit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure compressor running current on all three phases using a clamp meter — compare to the motor nameplate FLA.
- 2
Measure discharge and suction pressures to check for high head pressure or liquid slugging.
- 3
Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter.