U2

Abnormal High Discharging Temperature / Inner Thermostat (49C) Operation

Mitsubishi Electric · R410A Systems

¿Qué significa U2 ?

The compressor discharge temperature is excessively high OR the internal thermostat (49C) on the outdoor unit has activated due to an over-temperature condition. Both indicate an overheating issue within the outdoor unit or its components, risking compressor damage.

Causas comunes

  • High discharge temperature detected.
  • Operation of the inner thermostat (49C).
  • Overheating condition in the discharge line.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure discharge pressure and temperature at the compressor outlet using appropriate gauges and probes.

  2. 2

    Verify condenser coil cleanliness and ensure unrestricted airflow over the coil and around the compressor.

  3. 3

    Check refrigerant charge using manifold gauges and subcooling/superheat calculations — ensure it's not overcharged.

  4. 4

    Measure the temperature of the compressor casing using an infrared thermometer.

  5. 5

    Verify the operation and rotation direction of the outdoor fan motor.