Traduciendo...
001

Frequency Upper Limit Exceeded

Omron · MX2 Inverter

¿Qué significa 001 ?

This warning indicates that the parameter set for the frequency upper limit (A061) is configured to a value higher than the inverter's maximum allowed frequency (A004). This inconsistent setting may lead to unexpected operational limits or prevent the drive from reaching its full potential.

Causas comunes

  • Inadvertent manual input of A061 (Frequency Upper Limit) to a value greater than the drive's inherent maximum frequency (A004).
  • Software bug or corrupted parameter memory leading to an incorrect default value for A061 after a reset or firmware update.
  • Restoration of an incompatible parameter backup from a different drive model with a higher A004 setting.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Access parameter A061 (Frequency Upper Limit) and compare its value to A004 (Inverter Max Allowed Frequency).

  2. 2

    Set A061 (Frequency Upper Limit) to a value equal to or less than A004 (Inverter Max Allowed Frequency). A common practice is to set A061 to match A004 for maximum allowable speed.

  3. 3

    Confirm that the new setting for A061 is stored by powering the drive off and on, then verifying the parameter value again.

  4. 4

    If the issue persists, perform a parameter reset to factory defaults (e.g., P0-01 set to "99") and then re-enter all necessary application parameters carefully.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas