Traduciendo...
0101

CCW Limit Stop Input Signal

Omron · SYSMAC CJ Series PLC

¿Qué significa 0101 ?

This fault indicates that the pulse output operation was stopped due to a CCW limit signal input. This typically occurs during an origin search function, signifying that the machine has reached its negative travel limit, preventing further movement in the CCW direction.

Causas comunes

  • CCW limit switch physically activated during an origin search.
  • Miswiring of the CCW limit signal input, causing a false trigger.
  • Incorrect 'Limit Input Signal Type' (NC or NO) configured in PLC Setup for the CCW limit switch.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Manually move the driven axis in the CW (clockwise) direction until the CCW limit switch is physically disengaged.

  2. 2

    Measure continuity or voltage at the CCW limit input terminal to verify signal status (ON/OFF) and expected voltage level (e.g., 24VDC for ON, 0VDC for OFF) based on the configured 'Limit Input Signal Type' in PLC Setup.

  3. 3

    Access the PLC Setup 'I/O Module Tab Page' using CX-Programmer and verify the 'Limit Input Signal Type' parameter is correctly set to 'NC (Normally Closed)' or 'NO (Normally Open)' matching the physical switch.

Ver todos los códigos en este manual (20)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas