409

PCU RESET

Otis · DSD 412 DC Elevator Drive

¿Qué significa 409 ?

The PCU processor was unexpectedly reset. This can be due to improper PCU connections, incorrect software, hardware issues with the main circuit card, or external noise interference. If the problem persists, the Drive Control PCB may need replacement.

Causas comunes

  • Improper PCU connections.
  • Incorrect PCU software and revision level being used.
  • Possible problem with the main circuit card hardware.
  • External noise interference.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that PCU connections are proper and correct as necessary.

  2. 2

    Ensure that the correct PCU software and revision level is being used.

  3. 3

    Look for and eliminate external noise interference.

  4. 4

    Ensure that equipment and signal grounding connections are proper.

  5. 5

    If the problem remains, replace the Drive Control PCB.