Traduciendo...
905

FIELD LOSS FAULT

Otis · DSD 412 DC Elevator Drive

¿Qué significa 905 ?

The field current feedback has dropped below 80% of the expected current under specific operating conditions: during Field Weakening Mode (top speed, parameter #49), Full Field Mode (acceleration or deceleration, parameter #50), or Standing Field Mode (not running, parameter #53). This fault will shut down the drive.

Causas comunes

  • Open circuit failure in the motor field winding or its associated wiring.
  • Hardware failure within the motor field control circuitry.
  • Loss of power or incorrect phasing supplied to the Field Rectifier.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the motor field winding and wiring for any open circuits.

  2. 2

    Check the power supply and phasing to the Field Rectifier for correct operation.

  3. 3

    Test the motor field control circuitry for any hardware malfunctions.

  4. 4

    Review parameters #49, #50, and #53 to ensure they accurately reflect the expected field current values for the respective operating modes.

Ver todos los códigos en este manual (48)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Otis DSD 412 DC Elevator Drive