LINE VOLTAGE SETTING FAULT

Otis · DSD 412 DC Elevator Drive

¿Qué significa 919 ?

This fault is declared if the numerical value entered for the Rated Line Voltage (parameter #9) falls outside the acceptable range of 150 to 525VAC. Entering a value of 0 will default the rated voltage to either 230 or 460 VAC based on the sensed line voltage. A DSD power down is required.

Causas comunes

  • The value for parameter #9 (Rated Line Voltage) is configured outside the valid range of 150 to 525VAC.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Enter a value for parameter #9 (Rated Line Voltage) that is within the acceptable range of 150 to 525VAC.

  2. 2

    Perform a DSD power down after adjusting the parameter.