FIELD SENSE FAULT

Otis · DSD 412 DC Elevator Drive

¿Qué significa 925 ?

The field bridge rating is determined by a sense resistor on the Field Interface board, selected by SW1, which sets the motor field current feedback scaling for the A/D converter. If this resistance value is not recognized, a Field Sense Fault is declared, indicating a hardware fault on the Field Interface PCB, Drive Control PCB, or interconnecting cables and hardware. A DSD power down is required.

Causas comunes

  • The resistance value from the field sense resistor selected by SW1 on the Field Interface board is unrecognized.
  • Hardware fault on the Field Interface PCB.
  • Hardware fault on the Drive Control PCB.
  • Defective interconnecting cables or hardware, such as J13 not being properly seated.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check that connector J13 is properly seated on the Field Interface board.

  2. 2

    Verify the integrity of the interconnecting cable for any defects.

  3. 3

    Confirm that the correct field sense resistor is selected by SW1 on the Field Interface PCB.

  4. 4

    If problems persist, replace the Field Interface PCB or the Drive Control PCB.

  5. 5

    Perform a DSD power down after troubleshooting.