97
OVERSPEED FAULT
Otis · DSD 412 DC Elevator Drive
¿Qué significa 97 ?
The motor speed has exceeded the trip level configured in parameter #1, #11, or #12. Parameter #12 is a percentage of the motor speed value set in parameter #1, as measured by the encoder.
Causas comunes
- Incorrect setting of parameter #1, #11, or #12 above the motor's rated speed.
- Poor speed regulator tuning, indicated by incorrect values in parameters #40, #41, or #42.
- Velocity reference input is set above the motor's rated speed.
- Intermittent operation or signal loss from the velocity encoder.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check parameters #1, #11, and #12 to ensure the trip level is set below the motor's rated speed.
- 2
Verify and adjust the speed regulator tuning parameters #40, #41, and #42.
- 3
Inspect the velocity encoder and its connections for any intermittent operation or loose wiring.