Armature Circuit Open (Early Detection)
Otis · DSD 412 DC Elevator Drive
¿Qué significa F98 ?
This fault indicates that the motor's armature circuit is detected as open when the "Loop Confirm" signal activates, typically during the initial pre-loading sequence. This condition prevents the drive from establishing proper control of the motor and indicates a critical disconnection in the power path.
Causas comunes
- A physical break or disconnection in the motor armature circuit wiring.
- The main armature contactor is not closed or has failed to make proper contact.
- Faulty "Loop Confirm" sensor or feedback circuit providing an incorrect status of the armature circuit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Power down the drive, then inspect all connections in the motor armature circuit (e.g., motor terminals, contactor terminals) for looseness or damage.
- 2
Measure the resistance across the motor armature terminals to verify winding integrity and continuity.
- 3
Verify the main armature contactor is picking and its main power contacts are closing when commanded.
- 4
Check the wiring and functionality of the "Loop Confirm" feedback signal to ensure it accurately reflects the armature circuit status.