406
LOW LINE ALARM
Otis · DSD 412 Elevator System
¿Qué significa 406 ?
This alarm indicates that the input AC line voltage has sagged more than 10% below the nominal line voltage, as configured by parameter #9. This is a warning and does not automatically shut down the DSD 412 drive, but it suggests that preventative action may be required to avoid future F904 Low Line shutdown faults.
Causas comunes
- Insufficient or sagging 3 Phase Input AC Line Voltage.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the 3 Phase Input AC Line Voltage to verify its stability and level.
- 2
Verify that the nominal line voltage setting in parameter #9 accurately reflects the system's requirements.