924

FIELD CURRENT SETTING FAULT

Otis · DSD 412 Elevator System

¿Qué significa 924 ?

This fault is declared if a number entered for Rated Field Current #50 is outside the acceptable range of the Field Interface board, A3, current rating. This rating is determined by the field sense resistor selected by SW1 on the Field Interface PCB. This fault requires a DSD power down.

Causas comunes

  • Rated Field Current parameter #50 set outside the acceptable range of the Field Interface board, A3, current rating.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Enter a valid number for Rated Field Current, #50, within the acceptable range determined by the Field Interface board, A3, current rating and SW1 selection.

Ver todos los códigos en este manual (57)