925

FIELD SENSE FAULT

Otis · DSD 412 Elevator System

¿Qué significa 925 ?

The field bridge rating is determined by reading a sense resistor on the Field Interface board selected by SW1. If the resistance value is not recognized, a Field Sense Fault is declared, indicating a hardware fault. This fault requires a DSD power down.

Causas comunes

  • Hardware fault on the Field Interface PCB.
  • Hardware fault on the Drive Control PCB.
  • Fault in interconnecting cables or hardware.
  • J13 not seated properly.
  • Defective cable.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check that J13 is seated properly.

  2. 2

    Inspect the cable for defects.

  3. 3

    Verify the Field Interface board selection via SW1 and the sense resistor value.

  4. 4

    Replace the Field Interface PCB if faulty.

  5. 5

    Replace the Drive Control PCB if faulty.