Traduciendo...
F917

REVERSE ARM. V. FEEDBACK

Otis · DSD 412 Elevator System

¿Qué significa F917 ?

This fault is detected by the PCU Diagnostics function (Function #998) and indicates that the Armature Feedback wires are either reversed or not connected at all.

Causas comunes

  • Armature Feedback wires are incorrectly connected in reverse polarity.
  • Armature Feedback wires are not connected to the drive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Remove power from the drive.

  2. 2

    Inspect the Armature Feedback wires and reverse them if connected incorrectly.

  3. 3

    Verify that the Armature Feedback wires are securely connected.

  4. 4

    Repeat the PCU Diagnostics function to confirm the issue is resolved.

Ver todos los códigos en este manual (57)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas