Cross-circuit in Sensor Circuit 2
Phoenix Contact · ib il safe 2-eco
¿Qué significa 1 ?
A cross-circuit has been detected in sensor circuit 2, indicated by active cross-circuit detection. This condition occurs while sensor circuit 1 is active, the reset/start circuit is activated, and the segment circuit is open. This type of error can compromise the functional safety of the device by providing incorrect sensor input information.
Causas comunes
- Cross-circuit detected within sensor circuit 2
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Switch off the operating voltage to the device
- 2
Identify and physically remove the cross-circuit in sensor circuit 2
- 3
Perform a function test to verify correct device operation