Plausibility Error in Sensor Circuit 2 (External/Internal)
Phoenix Contact · ib il safe 2-eco
¿Qué significa 2 ?
This fault indicates either an external plausibility error in sensor circuit 2 or that internal diagnostics are active, signaling an internal error. This state occurs when both sensor circuits 1 and 2 are active, the reset/start circuit is activated, and the segment circuit is open. It suggests an inconsistency in sensor input logic or an internal device malfunction affecting functional safety.
Causas comunes
- External plausibility error detected in sensor circuit 2
- Internal diagnostics active, indicating an internal device issue
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
For external errors: Check the affected sensor circuit 2 for proper operation and signal integrity
- 2
For internal errors: Perform a power down reset (switch off and then re-apply operating voltage)
- 3
After addressing the error and performing any power down reset, conduct a subsequent function test