Traduciendo...
E-18
VIA Signal Fault
Schindler · Altivar 212 Variable Frequency Drive
¿Qué significa E-18 ?
This fault signifies that the analog input signal at terminal VIA has dropped below the minimum level defined by parameter F633 ([Loss of VIA]), indicating a potential loss of speed reference signal or sensor input.
Causas comunes
- The analog signal at terminal VIA is below the configured threshold.
- Incorrect setting of parameter F633 ([Loss of VIA]).
- Loss of signal from the sensor connected to VIA.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the analog signal voltage/current at terminal VIA.
- 2
Rectify the cause of the signal loss (e.g., sensor, wiring).
- 3
Check parameter F633 ([Loss of VIA]) and verify it is set correctly for the application.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Schindler Altivar 212 Variable Frequency Drive