Fd2

Closed Damper 2 Fault

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa Fd2 ?

This fault indicates that the damper is blocked open or soldered, preventing it from closing. This condition can affect temperature control or system operation by not restricting airflow as intended.

Causas comunes

  • Damper is blocked open or soldered.
  • Incorrect settings for damper feedback or relay control (F130, F132, F580).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Set parameter [Damper fdb type] (F580) to 0 (No feedback) or 1 (LI L set).

  2. 2

    Check the FL relay connection (FLA/FLB terminals) for proper wiring.

  3. 3

    Verify the relay configuration using parameters F130 ([RY Relay Function 1]) and F132 ([FL Relay Function]).