OCL
Short Circuit Motor Cable at Start
Schindler · Altivar 212 Variable Frequency Drive
¿Qué significa OCL ?
This fault indicates a phase-to-phase output short circuit or a low motor impedance detected in the motor or its wiring during startup by the Altivar 212 drive.
Causas comunes
- Phase-to-phase output short circuit in motor or cables.
- Motor impedance is too low.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Use a 1000 V testing tool (megger) to check the motor windings for phase-to-phase insulation resistance.
- 2
Use a 1000 V testing tool (megger) to check the motor cables for phase-to-phase insulation resistance.