OL1
Drive Overload
Schindler · Altivar 212 Variable Frequency Drive
¿Qué significa OL1 ?
This fault indicates that the Altivar 212 drive is overloaded, often due to excessively short acceleration times, high DC injection current, incorrect motor control settings, or a rotating load.
Causas comunes
- Acceleration time is too short (ACC or F500).
- DC injection current level (F251) is too high.
- Incorrect setting of [Mot cont. mode sel.] (Pt).
- Drive is starting into a rotating load.
- Excessive mechanical load is applied to the motor.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Increase the acceleration time parameters (ACC or F500).
- 2
Reduce the setting of parameters F251 ([DC braking current]) and/or F252 ([DC braking time]).
- 3
Select the correct setting for parameter [Mot cont. mode sel.] (Pt).
- 4
Enable catch on the fly function (F301).
- 5
Set parameter F302 ([Supply loss behav.]) to 2 (Freewheel).