Traduciendo...
OP1

Overvoltage During Acceleration

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa OP1 ?

This fault indicates an overvoltage condition during motor acceleration by the Altivar 212 drive, which can be caused by abnormal input voltage fluctuations, issues with the power network, or power factor capacitor switching.

Causas comunes

  • Input voltage is fluctuating abnormally.
  • Power network capacity is greater than 200 kVA.
  • Power factor capacitor switching in the supply network.
  • SCR switching on the power network.
  • Drive is starting into a rotating load.
  • Intermittent output phase fault.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Install a line reactor to mitigate input voltage fluctuations.

  2. 2

    Enable catch on the fly function (F301).

  3. 3

    Set parameter F302 ([Supply loss behav.]) to 2 (Freewheel).

  4. 4

    Determine the cause of any missing output phase (e.g., bad connection, output disconnect, open winding) and rectify it.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schindler Altivar 212 Variable Frequency Drive