Traduciendo...
OP2

Overvoltage During Deceleration

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa OP2 ?

This fault indicates an overvoltage condition during motor deceleration by the Altivar 212 drive, possibly due to excessively short deceleration times, overhauling loads, or fluctuating input voltage.

Causas comunes

  • Deceleration time is too short (dEC or F501).
  • Overhauling load on the motor.
  • Input voltage is fluctuating abnormally.
  • Power network capacity is greater than 200 kVA.
  • Power factor capacitor switching in the supply network.
  • SCR switching on the power network.
  • Drive is starting into a rotating load.
  • Intermittent output phase fault.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Increase the deceleration time parameters (dEC or F501).

  2. 2

    Enable parameter F305 ([Overvoltage fault]) for overvoltage prevention.

  3. 3

    Install a line reactor to mitigate input voltage issues.

  4. 4

    Check the input and output circuits for phase loss detection and rectify.

  5. 5

    Enable catch on the fly function (F301).

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schindler Altivar 212 Variable Frequency Drive